Voltage Drop Calculator and Solar Wire Size Calculator
Enter your system voltage, current and one-way wire length. The calculator shows the voltage lost in the wire, the voltage left at the load, the watts wasted as heat, and the smallest AWG wire that stays under your drop target without being too small for the current.
OffGrid Benchmark is reader-supported. Product links may earn us a commission at no cost to you. Full disclosure.
System Voltage
Current and Distance
Distance is one way, from source to load. The calculator doubles it for the round trip. If you are unsure of the current, use the rating of the fuse or breaker protecting the wire, which is the safer number.
Wire
Values outside 1 to 5 are clamped. Circuit type: DC only.
Your Results
Voltage Drop
1.24
volts (10.33%)
Voltage at Load
10.76
volts (of 12 V)
Power Lost in Wire
24.8
watts as heat
Smallest Wire for 3%
4
AWG, 2.57% drop
Too much drop. 10 AWG copper loses 10.33% at this current and distance, above your 3% target.
Formula: voltage drop = 2 x amps x ohms per 1,000 ft x one-way feet / 1,000. Resistance values are DC resistance at 75 C from NEC Chapter 9, Table 8. Ampacity is the 75 C column of NEC Table 310.16 and assumes a 30 C ambient and no more than three current-carrying conductors; heat, bundling, conduit fill and terminal ratings can lower it. Small copper sizes also face breaker limits under NEC 240.4(D). This is a planning tool, not a code design. Have a licensed electrician check any permanent or high-current system.
How the voltage drop formula works
Copper and aluminum resist current a little. That resistance turns some of the power into heat and drops the voltage at the far end of the wire. For a DC circuit the drop is:
Vd = 2 x I x R x L / 1000
I is the current in amps. R is the wire's DC resistance in ohms per 1,000 ft. L is the one-way length in feet. The 2 covers the return wire, since current travels out and back. Dividing Vd by the system voltage gives the percent drop, and multiplying Vd by the current gives the watts lost in the wire.
Worked example
Say a 12 V charge controller sits 25 ft from the battery and carries 20 A. With 10 AWG copper (1.24 ohms per 1,000 ft), the drop is 2 x 20 x 1.24 x 25 / 1000 = 1.24 V. That is 10.3 percent of 12 V, and 1.24 V x 20 A wastes 24.8 W as heat. Step up to 6 AWG (0.491 ohms) and the drop falls to 0.49 V, or 4.1 percent. At 4 AWG (0.308 ohms) it is 0.31 V, or 2.6 percent, with 6.2 W lost. So 4 AWG is the smallest copper wire that meets a 3 percent target. Its listed ampacity is 85 A, well above the 20 A load, so it passes the second check too.
The same load at 48 V needs only 5 A for the same 240 W. The drop on that 25 ft run in 10 AWG is 0.31 V, which is 0.6 percent of 48 V. This is why long runs favor higher voltage.
Why ampacity is a separate check
Voltage drop is about performance. Ampacity is about heat. A short, thick run can show almost no drop, and a short, thin run can show a small drop while still carrying more current than the insulation can take. The calculator checks both. For the full picture, including fuse placement and cable types, read what size wire for solar and series vs parallel panel wiring, since your wiring layout changes both the voltage and the current in the cable.
Safety. This is a planning tool, not a code design or an inspection. Real wire sizing depends on ambient temperature, bundling, conduit fill, terminal ratings, fuse or breaker size and your local code. Battery banks can deliver very high fault current. For permanent installs, or anything connected to a home, have a licensed electrician check the design and the work.
Where the numbers come from
- Resistance: DC resistance at 75 C from NEC Chapter 9, Table 8 (NFPA 70). I read the stranded uncoated copper values for 14, 12, 10 and 8 AWG (3.14, 1.98, 1.24 and 0.778) from a Mike Holt NEC textbook sample and an EC&M article. Larger sizes and the aluminum column match across two published summaries. I did not have a copy of the printed table, and some summaries list solid-wire values for small sizes, so check the figures against your edition of the NEC. I left out aluminum smaller than 6 AWG because the summaries disagree there.
- Ampacity: the 75 C column of NEC Table 310.16 as summarized here, for a 30 C ambient and no more than three current-carrying conductors.
- Temperature: resistance rises with heat, and the same textbook sample says copper at 90 C is about 5 percent higher than at 75 C. Hot attics and sunlit conduit run worse than the table.
Frequently Asked Questions
What is an acceptable voltage drop for a solar system?
This calculator defaults to 3 percent and lets you set anything from 1 to 5 percent. Lower is better because every lost volt is lost power, and low-voltage systems feel it most: 3 percent of 12 V is only 0.36 V. The NEC does not set one number for every circuit, so treat the target as a design choice and check your local code and equipment manuals.
Why does the calculator double the distance?
Current needs a complete loop. It leaves the source on the positive wire and returns on the negative wire, so both conductors lose voltage. The formula multiplies by 2 and uses the one-way distance, which is the length of one wire from source to load.
Does a low voltage drop mean my wire is safe?
No. Voltage drop and ampacity are separate checks. A short run of thin wire can show a tiny drop and still overheat at high current. That is why the calculator also checks the wire against the 75 C column of NEC Table 310.16 and warns when the current is above it. Fuse or breaker size and temperature derating still apply.
Should I use 12 V, 24 V or 48 V for a long wire run?
Higher voltage helps a lot. For the same power, 48 V draws a quarter of the current of 12 V, and wire loss scales with current squared. Try it above: enter the same power as amps at each voltage and compare the watts lost.
Can I use this calculator for AC wiring?
No. It uses DC resistance only, which fits panels, charge controllers, batteries and 12 V, 24 V or 48 V loads. AC circuits also involve power factor and reactance, and household AC wiring is a job for a licensed electrician.
What Size Wire for Solar
Wire gauge, fuses and cable types for panel, controller and battery runs.
Read the guideSeries vs Parallel Wiring
How your panel layout changes voltage and current, and so wire size.
Read the guide